Omega OMA-P1104 Cordless Telephone User Manual


 
Omegaphone
®
OMA-P1104 User’s Manual
38
4.7.2 Interrogating the Listen-in Time
To interrogate the Listen-in Time:
1. Press WHAT IS.
WHAT
IS
*
2. Press LISTEN TIME. The OMA-P1104 will recite the
listen time in seconds programmed.
9
LISTEN TIME
SOUND
4.8 Call Delay
Call Delay is the programmed length of time the OMA-P1104
waits, following detection of an alarm, before it begins the dial-
out sequence. This applies only to the first call. (Delay time
between calls is also programmable: refer to Intercall Time,
Section 4-11.)
The purpose for Call Delay is to allow time for personnel at the
OMA-P1104’s installation site to respond to and cancel an
alarm before dial-out begins. During this time, the OMA-P1104
will audibly repeat its “alert condition” message (unless the
Local Voice Mute feature has been activated—refer to Section
4.9). The default for Call Delay is 30 seconds. Call Delay can
be programmed from 0 seconds to 60 minutes (1 hour).
4.8.1 Programming the Call Delay
To program the Call Delay:
1. Press SET.
SET
#
2. Press CALL DELAY.
1
CALL
DELAY
The OMA-P1104 will respond: “Enter minutes.”