Device Alert
Configuration
Alert Levels
The Rosemount 708 provides 4 user configurable alerts.
Acoustic High - Triggers when acoustic level exceeds a user configured
threshold.
Acoustic Low - Triggers when acoustic level falls below a user configured
threshold.
Temperature High - Triggers when temperature level exceeds a user
configured threshold.
Temperature Low - Triggers when temperature level falls below a user
configured threshold.
Alert Setup
There are three methods that can be used to set up these alerts using AMS
Wireless Configurator or a field communicator.
Figure 5-3. Alert Setup screen
Alert Setup - Install and Learn
To use the install and learn function on the device to setup the alerts the
device must be installed and the equipment being monitored must be in its
normal state. After installation and operating conditions have been confirmed,
go to the configuration menu under guided setup and click on “alert setup.”
This will launch a dialog menu (Figure 5-3 on page 5-3), click on “Install and
Learn Alert Setup.” The application will then go through a series of steps that
will determine the current input conditions and set alerts based on this normal
operation (Figure 5-4).
If the input conditions are too close to the high or low measurement limits of
the device, the install and learn function will not be a good method to set the
alert levels. If this is the case, it is recommended that installation conditions
be checked and that the status is verified before moving ahead. If current
input conditions do not allow for the install and learn function, use the manual
or guided alert setup to set alerts.