ADTRAN 604 Telephone User Manual


 
Network Turnup Procedure Total Access 600 Series System Manual
40 © 2004 ADTRAN, Inc. 61200624L1-1B
Rackmounting the Total Access 612/616/624
Tools Needed
The Total Access 612/616/624 mount and connect with standard fasteners and hand tools:
Rackmount brackets (19”–P/N 1200627L1 or 23”–P/N 1200627L2)
Flat head screwdriver (medium)
Two Phillips head screwdrivers (small/medium)
Wire-wrap gun (optional)
25-pair male amphenol cable (customer connection)
Selected punch-down block and tool
Follow these steps to rackmount the Total Access 612/616/624:
6. SUPPLYING POWER TO THE UNIT
The Total Access 600 Series is not offered in DC powered versions. However, optional DC battery backup
systems are available for the Total Access 604/608 (P/N 1200641L1) and Total Access 612/616/624
(P/N 1175044L1, 2, or 4) systems.
AC Powered Systems
The AC powered unit comes equipped with a 3-prong, detachable power cord for connecting to a properly
grounded power receptacle. As shipped, the unit is set to factory default conditions. After installing the
unit it is ready for power-up. To apply power to the unit, ensure that it is properly connected to an
appropriate power source.
Rackmount Installation
Step Action
1.
Remove the wallmount brackets. (The Total Access 612/616/624 ships with wallmount
brackets attached.) Attach the mounting brackets to the side of the unit.
To avoid damaging the unit, use only the screws included in the mounting bracket
shipment when attaching mounting ears to the chassis.
2.
Position the Total Access 612/616/624 in a stationary equipment rack. This unit takes
up 1 RU of space. To allow proper grounding, scrape the paint from the rack around
the mounting holes where the Total Access 612/616/624 will be positioned.
3.
Have someone else hold the unit in position as you install two mounting bolts through
the unit’s brackets and into the equipment rack using a #2 Phillip’s screwdriver.
4.
Proceed to the steps given in
Supplying Power to the Unit
.
This unit shall be installed in accordance with Article 400 and 364.8 of the NEC NFPA
70 when installed outside of a Restricted Access Location (i.e., central office, behind a
locked door, service personnel only area).
Power to the Total Access 600 Series AC system must be from a grounded 90-130 VAC,
50/60 Hz source.
Verify the power receptacle uses double-pole, neutral fusing.
Maximum recommended ambient operating temperature is 45 ºC.