Power, Battery, & Ground Wiring
Power Wiring
NOTE: DO NOT APPLY POWER UNTIL THE INSTALLATION IS
COMPLETE. TURN MASTER POWER SWITCH OFF BEFORE
WIRING.
1. Route two wires between the AE-1000 and the power transformer.
For power wire runs up to 100 feet, use 18 AWG, THHN 600-volt
insulated wire.
For power wire runs up to 200 feet, use 16 AWG, THHN 600-volt
insulated wire.
2. Connect the wires to the transformer. Connect the other end of the
wires to the AE-1000 AC1 & AC2 terminals.
Backup Battery / Uninterruptable Power Supply
Use of battery backup is optional. It will allow the AE-1000 to operate for
short periods of time without AC power. The door or gate access device
must use some type of battery backup of its own for the entire system to
be functional.
A backup battery will not fi t into the AE-1000 case. Protect the backup
battery inside a rain-tight NEMA enclosure suitable for the installation.
NOTE: A backup battery is not required to maintain the AE-1000
clock/calendar and programming memory during power outages.
1. Route two wires between the AE-1000 and the backup battery.
2. Connect the Battery positive to the AE-1000 DC+ terminal and the
negative to the DC- terminal.
NOTE: The AE-1000 does not supply battery charging current.
An external battery charger will be required to maintain the battery.
Earth Ground
For the best ground, use size 12 gauge solid wire or larger to connect the
to an 8-foot copper ground rod. Locate the ground rod next to the Power
and Telephone company rods and bond the rods together with a new
clamp. Do not disturb the clamps installed by the Power or Telephone
Company. Alternately, connect to a metallic cold water pipe for the earth
ground.
1. Connect the wire from the earth ground to the AE-1000’s EARTH
GROUND STUD.
RS-232 Port
A modular connector is provided for the bi-directional 38.4K baud
RS-232 port. The AE-1000’s RS-232 port connects to a personal
computer’s COM port. System programming can be performed locally
with a computer connected to the RS-232 port.
16 VAC
35 VA
TRANSFORMER
EARTH
GROUND
STAKE
12 VOLT
BATTERY
POWER
TERMINALS
EARTH
GROUND
STUD
NOTE: THE OPTIONAL
BACKUP BATTERY
WILL REQUIRE AN
EXTERNAL CHARGER
DC
DC
AC2
AC1
AE-1000
RS-232 PORT
COMPUTER'S
COM PORT
LINEAR MODEL A2C
SERIAL COMPUTER CABLE
SET COMPUTER COM PORT
BAUD RATE TO 38,400 BPS
NOTE: USE A DB-25 TO DB-9 CABLE ADAPTER IF REQUIRED