![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/0/c1/0c11c45b-a36f-44c2-93cb-e393ff136533/0c11c45b-a36f-44c2-93cb-e393ff136533-bg28.png)
SUPER ABSORPTIONENVIRONMENTALLY FRIENDLY TECHNOLOGY
Generator temp 69.9°C
MODE
STOP RUN
CHILLER
BUZZER STOP
STOP LOCAL
REMOTE
OPERATION
ALARM
REF PUMP
ABS PUMP
PURGE PUMP
SETTING
Name Lamp color
Running(Operation) indication lamp Red
Stop indication lamp Green
Alarm indication lamp Orange
Remote / Local select button with lamp Red
Mode select button with lamp Red
Data display LCD
symbol
Control panel (LE)
Hot water control valve
ø21 (LE-01 thru LE-12)
ø27 (LE-13 thru LE-24)
ø21 (LE-31 thru LE-53)
Power supply ø33
Remote control ø27
500
300
30
1400
Table 13. Indication lamp
Foundation dimensional data (LE)
Figure 58. LE-01 Thru 53
150
A
B
B
D
C
E F
G
J
K
AA
BB
Model
No.
Weight (kg) Dimensions (mm)
2,300 1,150 1,150 1,426 — 113 226 800 100 1,000 125 900
2,400 1,200 1,200 1,426 — 113 226 800 100 1,000 125 900
2,800 1,400 1,400 1,926 — 113 226 800 100 1,000 125 900
3,900 1,950 1,950 1,896 — 125 250 800 100 1,000 150 900
4,100 2,050 2,050 1,896 — 125 250 800 100 1,000 150 900
5,100 2,550 2,550 2,916 — 125 250 800 100 1,000 150 900
5,400 2,700 2,700 2,916 — 125 250 800 100 1,000 150 900
6,500 3,250 3,250 2,916 — 125 250 1,000 100 1,200 150 1,100
6,900 3,450 3,450 2,916 — 125 250 1,000 100 1,200 150 1,100
8,000 4,000 4,000 3,936 — 125 250 1,000 100 1,200 150 1,100
8,500 4,250 4,250 3,936 — 125 250 1,000 100 1,200 150 1,100
10,300 5,150 5,150 3,886 — 150 300 1,100 100 1,300 200 1,200
10,800 5,400 5,400 3,886 — 150 300 1,100 100 1,300 200 1,200
12,500 6,250 6,250 3,886 — 150 300 1,150 100 1,350 200 1,250
13,000 6,500 6,500 3,886 — 150 300 1,150 100 1,350 200 1,250
17,700 8,850 8,850 3,966 130 110 350 1,600 100 1,800 250 1,700
19,200 9,600 9,600 4,508 130 110 350 1,600 100 1,800 250 1,700
20,600 10,300 10,300 5,006 130 110 350 1,600 100 1,800 250 1,700
LE-01
LE-02
LE-03
LE-11
LE-12
LE-13
LE-14
LE-21
LE-22
LE-23
LE-24
LE-31
LE-32
LE-41
LE-42
LE-51
LE-52
LE-53
Oper.
AA BB A B C D E F G J K
Table 12. Dimensional data
Figure 59. Control panel
NOTES :
1. The base of machine has ø50 hole for anchor bolt.
2. Anchor bolt should be fixed by shown detail drawing.
Washer should be welded with base.(Refer to Figure 21 page32)
3. There should be a drain ditch around the foundation.
4. The floor surface should be made as water proof for ease of
maintenance work.
5. Surface of foundation should be made flat.
6. Anchor bolts and nuts are supplied by customer.