A SERVICE OF

logo

3
1-6. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
direct sunlight.
nearby heat sources that may affect performance of
the unit.
areas where leakage of flammable gas may be
expected.
places where large amount of oil mist exist.
DO:
select an appropriate position from which every corner
of the room can be uniformly cooled. (High on a wall
is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have
the shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation differ-
ence (H) above or below the outdoor unit and within a
total tubing length (L) from the outdoor unit as detailed
in Table 3 and Fig. 3a.
Table 3
6 inches
min.
6 inches
min.
6 inches min.
Front View
Fig. 2
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Elevation
difference (H)
Fig. 3a
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
(ft.) (ft.) (ft.) (oz./ft.)*
C2432, CL2432 25 132 50 0.27
WARNING
To prevent abnormal heat gen-
eration and the possibility of
fire, do not place obstacles,
enclosures and grilles in front
of or surrounding the air condi-
tioner in a way that may block
air flow.
* If total tubing length becomes 25 to 132 ft. (max.), additional refrigerant (R22) charge of 0.27 oz./ft. is required.
No additional charge of compressor oil is necessary.
Indoor unit
Floor level
Wall
Minimum height
from floor level
5 ft.
Fig. 3b
For stable operation of
the air conditioner, do
not install wall-mounted
type indoor units less
than 5 ft. from floor
level.
CAUTION
Drain hose
Indoor unit
Outside drainage
Fig. 1
01-386 AirCon 12/11/01 4:48 PM Page 3