Site Planning Data, Series 610, 1000kVA, Multi-Module Systems
66
System Control Cabinets
Multi-Module Systems are provided with a System Control Cabinet. Cabinets are available to match load current. Table 8 shows dimensions and
weights for SCCT cabinets.
Table 6 Site planning data—600V input
UPS
Rating
AC Output
Voltage Options
Rectifier AC
Input Current
Inverter AC
Output Current
Required
Battery
Disconnect
Rating (A)
Max. Battery
Current
at End of
Discharge (A)
% Efficiency
at Full Load
Max. Heat
Dissipation
Full Load
BTU/h (kWH)
Dimensions
Approx. Weight
Unpacked
Floor Loading
Distributed Loading
kVA kW VAC
Input
Filter Nom Max Nom Max
WxDxH:
in. (mm) lb. (kg) lb./ft.
2
(kg/m
2
)
1000 900 600 No 1096 * 1369 962 1203 2500 2440 93 231,203 (67.7)
177x44x82
(4496x1118x2083)
16555 (7509) 306 (1494)
1000 900 600 Yes 1012 ** 1265 962 1203 2500 2440 93 231,203 (67.7) 17400 (7893) 322 (1572)
See Notes (p. 65): 13 1,4,5,7,8,9,11,12 2,5,7,8,9,11,12 6 6,8,9,11,12 14,15 14,15
* Nominal Input Power Factor 0.85 lagging at full load; 0.09 Maximum Total Input Harmonic Current Distortion (THD) at full load.
** Nominal Input Power Factor 0.92 lagging at full load; 0.04 Maximum Total Input Harmonic Current Distortion (THD) at full load.
Table 7 Site planning data—480V input
UPS
Rating
AC Output
Voltage Options
Rectifier AC
Input Current
Inverter AC
Output Current
Required
Battery
Disconnect
Rating (A)
Max. Battery
Current
at End of
Discharge (A)
% Efficiency
at Full Load
Max. Heat
Dissipation
Full Load
BTU/h (kWH)
Dimensions
Approx. Weight
Unpacked
Floor Loading
Distributed Loading
kVA kW VAC
Input
Filter Nom Max Nom Max
WxDxH:
in. (mm) lb. (kg) lb./ft.
2
(kg/m
2
)
1000 900 480 No 1369 * 1712 1203 1504 2500 2440 93 231,203 (67.7)
177x44x82
(4496x1118x2083)
16555 (7509) 306 (1494)
1000 900 480 Yes 1265 ** 1582 1203 1504 2500 2440 93 231,203 (67.7) 17400 (7893) 322 (1572)
See Notes (p. 65): 13 1,4,5,7,8,9,11,12 2,5,7,8,9,11,12 6 6,8,9,11,12 14,15 14,15
* Nominal Input Power Factor 0.85 lagging at full load; 9% Maximum Total Input Harmonic Current Distortion (THD) at full load.
** Nominal Input Power Factor 0.92 lagging at full load; 4% Maximum Total Input Harmonic Current Distortion (THD) at full load.
Table 8 System Control Cabinet data - SCCT
Type Amps Overall dimensions - WxDxH: in. (mm) Weight - lb. (kg)
SCCT 1200 37x37x78 (940x940x1981) 1000 (454)
SCCT 1600 62x48x78 (1575x1219x1981) 1525 (692)
SCCT 2000 62x48x78 (1575x1219x1981) 2850 (1293)
SCCT 2500-3000 62x60x78 (1575x1524x1981) 3100 (1406)
SCCT 4000 138x60x78 (3505x1524x1981) 5850 (2653)